AHEAD OF THE FLOW
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
2
ELEVATION VIEW OF INDICATOR POST AND VALVE
17-4 Kennedy Valve/Indicator Posts
1
1
/4" Sq.
1" Sq. Stem
9"
36
3
/4"
5
1
/8"
30"
6" Dia.
12" Dia.
Trench
Depth
Ground Line
Standpipe
(painted red)
Standpipe
(painted black)
Top Section
max. = 10"
min. = 7"
INDICATOR POST STYLE 2945
FIXED LENGTH UL/FM
DIMENSIONS AND INSTRUCTIONS
KENNEDY VALVE
Available in Sizes F G H
See Page 6 for Dimensions
FIELD ADJUSTMENT
INSTRUCTIONS
1. Remove the top section from the top of the
Indicator Post assembly.
2. Cut the required length off the bottom of th
e
Standpipe for the Ground Line to match up
with Standpipe Ground Line mark.
3. Cut the 1" Sq. Stem at a distance of 9"
above the top of the Standpipe.
4. Set the “OPEN” and “SHUT” targets for th
e
appropriate valve size.
5. Reattach the Top Section to the top of the
Indicator Post assembly.
Updated 05/02/2012
Fig. 2 Fig. 3